| KRAUS & NAIMER | L400 - Electrical Data | 5.11.2004 |
| Approved | Confirms to requirements | No listing required |
| CSA, CUL, CULUS, UL | BS EN, CH, GOST, IEC, VDE | D, FI, N, ÖVE, S |
| Rated Operational Voltage Ue | 690V | 1) | ||
| Rated Insulation Voltage Ui | 690V | 1) | ||
| Rated Thermal Current Iu/Ith | 500/500A (Ambient temperature +35°C during 24 hours with peaks up to +40°C / Ambient temperature +55°C during 24 hours with peaks up to 60°C) | 2) | ||
| Rated Operational Current Ie | ||||
| AC-20A No-load operation |
|
500A | 2) | |
| AC-20B Occasional switching under load cos Phi 0,8 3 phase, 3 pole and 1 phase, 2 pole |
|
500A | 2) | |
|
|
450A | 2) | ||
|
|
350A | 2) | ||
| AC-21B Occasional switching of resistive loads, including moderate overloads 3 phase, 3 pole and 1 phase, 2 pole |
|
450A | 2) | |
|
|
400A | 2) | ||
|
|
300A | 2) | ||
| Rated Utilization Category | ||||
| AC-23B Occasional switching of motors or other high inductive loads 3 phase, 3 pole |
|
75kW | 2) | |
|
|
132kW | 2) | ||
|
|
132kW | 2) | ||
|
|
65kW | 2) | ||
| Rated Voltage | 600V | 1) | |
| Rated Insulation Voltage Ui | 600V | 1) | |
| Rated Thermal Current | 400A | 1) | |
| Interrupting Rating |
|
300A | 1) |
| Minimum Voltage | 20V | |||
| Rated Impulse Withstand Voltage Uimp | 6kV | 1) | ||
| Short Circuit Protection | ||||
| Max. fuse size (aR-characteristic) | 500A | |||
| Rated short-time withstand current (1s-current) | On request | |||
| Ambient Temperature of Stages (for switches with electro-mechanical accessories refer to optional extra) | ||||
| open at 100% Iu/Ith | 55°C during 24 hours with peaks up to 60°C; Permissible load see Rated Thermal Current | |||
| Terminal lead material | copper wires only | |||
| For connections with cable terminal or copper busbar | ||||
| Connecting screw | M12 | |||
| Length of connecting screw | 30mm | |||
|
|