GM MultiVolt Series
24 Hour, 7 Day

  • 120, 208/240 or 277VAC
  • 30A, 2 HP @ 240V switch
  • Indoor or outdoor enclosure
  • Captive trippers with interval of
    15 minutes on 24 hour model
  • Easy to set clock face timer
  • Optional clear cover allows viewing timer clock face without opening cover
  • Fits into competitive enclosures

 

  • All models can be powered by 120, 208/240 or 277VAC.
  • Captive trippers are easy to set, can't be lost.
  • 96 trippers provide up to 48 on/off events on 24 hr. model.
  • 84 trippers provide up to 42 on/off events on 7 day model.
  • Authentic clock face with hour and minute hands on both 24 hr. and 7 day models.
  • Synchronous drive for low cost and greatest accuracy.
  • Quartz drive for 7 day carry-over with rechargeable Nicad battery.
  • Three way, OFF/AUTO/ON override switch provides continuous override.
  • Replaces Intermatic, Tork, and Paragon time switches.
  • UL Listed.
Specifications

Switch Rating: SPDT and DPDT switch models

Normally Open Contacts:
30A General Purpose/Res @ 277V
1 HP; 96ALR, 20AFL @ 120V
2 HP; 72ALR, 12AFL @ 240V
15A, 1800W Tungsten @ 125V
5A, 1250W Tungsten @ 250V
20A Ballast @ 120-277V
1A Pilot Duty @ 120-240V
20A Resistive @ 28VDC
Normally Closed Contacts:
15A General Purpose/Res @ 250V
6A General Purpose/Res @ 277V
1/4 HP @ 125V, 1/2 HP @ 250V
3A, 750W Tungsten @ 125-250V
3A Ballast @ 120-277V
1A Pilot Duty @ 120-240V
15A Resistive @ 28VDC

NOTE: If loads are connected to both NC and NO contacts, both contacts are derated to 67% of the above values.

Wiring Connections: Screw clamp terminals accommodate up to two #10AWG wires.

Environmental Ratings:
Operating Temperature Range: -40°F to 130°F, Synchronous Units; -20°F to 130°F, Quartz Units
Operating Humidity: 0 to 95% non-condensing

Enclosures:
Indoor: Plastic, pale gray, NEMA 1 or metal, gray, NEMA 1
Outdoor: Plastic, dark gray, NEMA 3R raintight

Dimensions: 10" x 6.5" x 3.75" deep

Shipping Weight: 2 lbs.

Specifiers Guide
Furnish and install a Grasslin GM ___ MultiVolt Series 24 hour (7 day) time switch with captive trippers and quartz (synchronous) drive. Input voltage shall be 120, 208/240 or 277VAC on all units and SPDT (DPDT) contacts shall be rated at 30A, 2 HP @ 240V. To set the starting time and to provide time indication, the unit shall have an authentic clock face with hour and minute hands. Enclosure to be NEMA 1 (NEMA 3R raintight). Time switch shall contain an OFF/AUTO/ON manual override.

For Carry-over: The time switch shall have a quartz drive with 7 day reserve carry-over.