GM Digi Photo


 GM Digi Series
24 Hour, 7 Day

  • 30A, 2 HP @ 240V switch
  • Indoor or outdoor enclosure
  • Rechargeable battery backup with
    1 week or more carry-over
  • Optional clear cover allows viewing timer display without opening cover
  • GM digi 42 models have holiday program and automatic daylight time changeover
  • All models can be powered by 120, 208/240 or 277V AC.
  • 24 hour or 7 day programming with accuracy to the second.
  • Easy programming; minimal keys and programming steps.
  • Selectable blocks of weekdays or weekends for quick programming.
  • Automatically recharged NiCad battery maintains program and display for one week or more.
  • Manual override provides for either temporary or continuous ON or OFF state.
  • Replaces Intermatic, Tork, and Paragon time switches.
  • UL Listed.
Specifications

Switch Rating: SPDT and DPDT switch models

NO Contacts:
30A General Purpose/Res @ 277V
1 HP; 96ALR, 20AFL @ 120V
2 HP; 72ALR, 12AFL @ 240V
15A, 1800W Tungsten @ 125V
5A, 1250W Tungsten @ 250V
20A Ballast @ 120-277V
1A Pilot Duty @ 120-240V
20A Resistive @ 28VDC
Normally Closed Contacts:
15A General Purpose/Res @ 250V
6A General Purpose/Res @ 277V
1/4 HP @ 125V, 1/2 HP @ 250V
3A, 750W Tungsten @ 125-250V
3A Ballast @ 120-277V
1A Pilot Duty @ 120-240V
15A Resistive @ 28VDC

NOTE: If loads are connected to both NC and NO contacts, both contacts are derated to 67% of the above values.

Wiring Connections: Screw clamp terminals accommodate up to two #10AWG wires.

Environmental Ratings: Operating Temperature Range: –20°F to 131°F (–29°C to 55°C)

Operating Humidity: 0 to 95% non-condensing

Programming: Up to 42 programs per channel: consist of one or more days of the week, and an ON or OFF time.

Shortest switching time 1 minute.

Enclosures:
Indoor: Plastic, pale gray, NEMA 1 or metal, gray, NEMA 1
Outdoor: Plastic, dark gray, NEMA 3R raintight

Dimensions: 10” x 6.5” x 3.75” deep

Shipping Weight: 2 lbs.

Specifiers Guide
Furnish and install a Grasslin GM ___ electronic time switch. This one channel control shall have 24 hour and 7 day programming and include block programs for different weekday schedules. The LCD shall display time of day in AM/PM format and provide load status indication. A daylight time adjustment key shall also be provided. The time switch will be programmable to the minute and also offer a manual override for ON or OFF to the next scheduled event or for permanent ON/AUTO/OFF. The SPDT (DPDT) relay output will be rated for 30A, 2HP @ 240VAC. Carry-over shall be provided for a minimum of 7 days with a built-in rechargeable NiCad battery which need not be replaced. Enclosure to be NEMA 1 (NEMA 3R raintight).