GMX digi Series

  • 16A @ 240V switch
  • SPDT switching
  • 12, 20 or 42 programs
  • Indoor or outdoor enclosure
  • 24 hour and 7 day programming
  • GMX digi 42 models have holiday program and automatic daylight time changeover
  • One and two channel models
  • Rechargeable battery backup with 1 week or more carry-over
  • Manual override
  • Optional clear cover allows viewing timer display without opening cover
  • Fits into competitive enclosures
  • A low cost alternative for applications that require only 16A switching.
  • 24 hour or 7 day programming with accuracy to the second.
  • Easy programming; minimal keys and programming steps.
  • Selectable blocks of weekdays or weekends for quick programming.
  • Automatically recharged NiCad battery maintains program and display for one week or more.
  • Manual override provides for either temporary or continuous ON or OFF state.
  • Replaces Intermatic, Tork, and Paragon time switches.
  • UL Listed.
Specifications
SPDT Switch Rating: 16A Resistive @ 250VAC
1000W Tungsten @ 250VAC

Shortest Switching Time: 1 minute

Environmental Ratings:
Operating Temperature Range: –20°F to 140°F
Operating Humidity: 0 to 95% non-condensing

Wiring Connections: Screw terminals for up to #12AWG wire

Enclosures:
Indoor: Plastic, pale gray, NEMA 1
Outdoor: Plastic, dark gray, NEMA 3R raintight

Specifiers Guide
Furnish and install Grasslin GMX digi ___ 120 (240) volt electronic time switch. This one channel control shall have 24 hour and 7 day programming and include block programs for different weekday schedules. The LCD shall display time of day in AM/PM format and provide load status indication. A daylight time adjustment key shall also be provided. The time switch will be programmable to the minute and also offer a manual override for ON or OFF to the next scheduled event or for permanent ON/AUTO/OFF. The SPDT relay output will be rated for 16A @ 240VAC. Carry-over shall be provided for a minimum of 7 days with a built-in rechargeable NiCad battery which need not be replaced. Enclosure to be NEMA 1 (NEMA 3R raintight).